Specification :
Detailed Product Description
ABC cable/ overhead cable/ aerial cable/ can be made according to the BS, IEC, ASIN, DIN, JIS, CSA standards. 1KV, 10KV, etc.
ABC cable/ overhead cable/ aerial cable/ can be made according to the BS, IEC, ASIN, DIN, JIS, CSA standards. 1KV, 10KV, etc.
Aerial Bundle Cable ( ABC cable) , 0.6/ 1KV, XLPE insulation, Aluminum Conductor
Product Description
1. Application of Service Drop Cable:
Service Drop Cable ( ABC CABLE) is mainly used for electric power transmission, rebuilding of urban and forest regions. They can improve the safety and reliability of electrified wire netting.
2. Type of Service Drop Cable:
Service Drop Cable ( ABC CABLE) covers mainly three types:
Duplex Service Drop
Triplex Service Drop
Quadruple Service Drop
The cable can be produced whose construction is phase conductor with neutral bare conductor or phase conductor with insulated neutral conductor, etc. And we can still produce the cables according to the request of customers.
3. Detailed Introduction of Service Drop Cable
3.1 Duplex Service Drop
Applications
To supply 120 volt aerial service for temporary service at construction sites, outdoor or street lighting. To be sued for service at voltage of 600 volts or less and at conductor temperature not to exceed 75 degree.
Construction
Concentric strand or compressed 1350-H19 conductor, polyethylene or cross linked polyethylene insulation, concentric strand AAC, ACSR, or 6201 alloy neutral messenger.
Cord word Phase conductor Bare neutral messenger Nominal lay length Weight per 1000ft ( ibs) Allowable amp cities
Size
( AWG) Stranding Insulation Thick( Mils) Size
( AWG) Stranding Pated strength( ibs) inches XLPE PE XLPE PE
AAC Neutral-messenger
Pekingese 6 1 45 6 7 563 10.36 61 61 85 70
Collie 6 7 45 6 7 563 10.36 64 64 85 70
Dachshund 4 1 45 4 7 881 10.36 92 92 115 90
Spaniel 4 7 45 4 7 881 10.36 96 96 115 90
Doberman 2 7 45 2 7 1350 14.88 147 147 15 0 120
Malamute 1/ 0 9 60 1/ 0 7 1990 14.88 234 234 205 160
3.2 Triplex Service Drop
Applications
To supply power from the utility’ s lines to the consumer’ s service head. For service at 600 Volts or less ( phase to phase) at a conductor temperature of 75 degree maximum for PE insulation or 90 degree maximum for XLPE insulation.
Construction
Concentric strand or compressed 1350-H19 conductor, polyethylene or cross linked polyethylene insulation, concentric strand AAC, ACSR, or 6201 alloy neutral messenger.
Cord word Phase conductor Bare neutral messenger Nominal lay length Weight per 1000ft ( ibs) Allowable amp cities
Size
( AWG) Stranding Insulation. Thick( Mils) Size
( AWG) Stranding Pated strength( ibs) inches XLPE PE XLPE PE
AAC Neutral-messenger
Patella 6 7 45 6 7 563 14.88 103 103 85 70
Oyster 4 7 45 4 7 881 14.88 154 154 115 90
Clam 2 7 45 2 7 1350 20.58 233 233 150 120
Murex 1/ 0 7 60 1/ 0 7 1990 20.58 374 374 205 160
Purpura 1/ 0 9 60 1/ 0 7 1990 20.58 368 368 205 160
Nassa 2/ 0 7 60 2/ 0 7 2510 25.42 462 462 235 185
Melita 3/ 0 17 60 3/ 0 19 3310 29.97 562 562 275 215
Portunus 4/ 0 18 60 4/ 0 19 4020 29.97 696 696 315 245
Nannynose 336.4 19 80 336.4 19 6146 38.79 1118 1118 420 325
3.3 Quadruple Service Drop
Applications
Used to supply 3 phase power, usually from a pole-mounted transformer to the use` s service head where connection to the service entrance cable is made. To be used at voltages of 600 volts or less phase to phase and at conductor temperature not to exceed 75 for PE insulated conductors or 90 for XLPE insulated conductors.
Construction
Conductors are concentrically stranded, compressed 1350-H19 aluminum, and insulated with PE or XLPE. Neutral messengers are concentrically stranded 6210 AAAC, AAC or ACSR
Cord word Phase conductor Bare neutral messenger Nominal lay length Weight per 1000ft ( ibs) Allowable ampacities
Size
( AWG) Stranding Insulation. Thick( Mils) Size
( AWG) Stranding Pated strength( ibs) inches XLPE PE XLPE PE
AAC Neutral-messenger
Clydesdale 4 1 45 4 7 881 20.58 198 198 100 80
Pinto 4 7 4 5 4 7 881 20.58 211 211 100 80
mustang 2 7 45 2 7 1350 25.42 318 318 135 105
Criollo 1/ 0 9 60 1/ 0 7 1990 25.42 503 503 180 140
Percheron 2/ 0 11 60 2/ 0 7 2510 29.97 619 619 205 160
Hanovarian 3/ 0 17 60 3/ 0 19 3310 35.18 764 764 2 35 185
Oldenburg 4/ 0 18 60 4/ 0 19 4020 35.18 945 945 275 210
Lippizaner 336. 40 19 80 336.4 19 6146 38.79 1519 1519 370 280
Standards
1. B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
2. B-231 Aluminum Conductors, Concentric-Lay-Stranded.
3. B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced ( ACSR) .
4. B-399 Concentric-Lay Stranded 6201-T81 Aluminum Alloy Conductors.
5. B498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced ( ACSR) .
6. Duplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ ICEA S-76-474