Smart SCADA Alarm Systems[May. 30, 2011 4:44:21]
This System Using for supervising & alarming of electric data, which integrates environment,
remote collection and supervision of electric data, fire, burglar-proof function with remote controlling,
which is widely used in the equipment room of electricity, telecommunications, petroleum, and chemical industry.
To properly operate this system, please read through this manual before using this product.
Besides, qualified electrician is required to install and test this system due to this system demands the connection of AC & DC power.
1. Main function:
a. Built-in standard frequency : GSM module 900/ 1800/ 1900MHZ ( 850/ 900/ 1800/ 1900MHZ optional)
b. To pick up SMS from electric data, fire and burglar alarm by setting one to phone No. in one to four group.
c. Phonetic dialing burglarproof function can be materialized by setting phone No.in one to two group.
d. Four simulating route of picking up data: the dada-collecting and setting of alarming value through four routes of AC voltage , DC voltage, temperature, standard DC from 0 to 20mA.
e. Two routes of relay to control output
f. Two switches for inputting ( wired guarding zone)
g. One wireless SOS zone.
h. One wireless fire alarm.
i. Six wireless zone.
j. Alarm when power’ s failure.
k. Alarm in case of dismantling mainframe.
l. Programming by wireless digital keypad or SMS.
m.On-the-spot monitor ( standard) & two-way remote communication ( optional) .
n. Built-in pre-recorded function by user itself.
o. User-define the report of the daily operating status of mainframe.
2. Technical Parameters
a. GSM module : 900/ 1800/ 1900MHZ ( standard) 850/ 900/ 1800/ 1900MHZ ( universal function , optional)
b. Wireless accessories : 315MHZ ( standard) 433MHZ ( optional)
c. Working power :
Type: Switch power
Input: AC 220V or 110V ( Max.260V) , 50 or 60 HZ.
Output: DC 15V/ 2A
d. Backup battery.
Type: lead-acid battery
Rated voltage: 12V ( Max.13.8V)
Current capacity: 1200 mAh
e. The power consumption of host in case of standby: 0.9W
f. The input of AC voltage:
Voltage range of inputting : 0-300, 50HZ ( standard) , 60HZ ( optional) :
High voltage proof: 2500VDC ( leakage: 1mA, 1minute )
Precision : ± 1%
g) .Input of DC voltage:
Voltage range of inputting: 0 - 60V
High voltage proof: 2500VDC ( Leakage: 1mA, 1minute)
Precision : ± 1%
h. Temperature collecting:
Survey range : -10-+ 60° C
Temperature range of thermal sensor: -55-+ 150° C
Precision : ± 1%
i. Input route of AC:
Input limit : 0-20mA
Precision : ± 1%
Accessible to sensor with DC output range from 4 to 20mA
j. Switch ( Wired guarding zone)
Dry connection.
User-define the contact junction of NC or NO.
k. Relay to control output : Contact junction type: N.O.
Capacity of contact junction : 7A/ 240VAC, 1 0A/ 1 20VAC, 1 0A/ 28VDC.
l.User-define recording time: not more than 8s
m.The driver of voice speaker: 8 ohms, 0.25W
n. The driver of warning signal: DC9-15V, 1 20mA
o. The volume & weight of mainframe:
Volume: 29cm X 25.5cm X 8.1cm
Weight: 2.8KG
p. Storing temperature: -40 - + 85° C
q. Working temperature: -10 - + 60° C
r. Indoor wall-mounting installment