Specification :
Application and Description
These cables are designed for the internal wiring of switchboards and distributor boards with an alternating
nominal voltage up to 1000 Volts or a direct voltage up to 750 volts. Generally install in pipes or ducts and
internal wiring of appliances with maximum operating temperature of 90º C, and generally in areas ( such as
public and government buildings) where smoke and toxic fumes may cause a threat to life and equipment.
The cables produce no corrosive gasses when burnt which is particularly important where electronic
equipment is installed.
Standard and Approval
HD 22.9 S2, VDE-0282 Part-9, BS 7211, IEC 60754-2, EN 50267, VDE 0482-267, CE Low Voltage
Directive 73/ 23/ EEC and 93/ 68/ EEC, ROHS compliant
Cable Construction
- Fine bare copper strands
- Strands to VDE-0295 Class-5, IEC 60228 Class-5 BS 6360 cl. 5, HD 383
- Cross-link polyolefin EI5 core insulation
- LSOH - low smoke, zero halogen
Technical Characteristics
- Working voltage: 300/ 500v ( H05Z-K) , 450/ 750v ( H07Z-K)
- Test voltage: 2500 volts
- Flexing bending radius: 8 x Ø
- Static bending radius: 8 x Ø
- Flexing temperature: -15º C to + 90º C
- Static temperature: -40º C to + 90º C
- Flame retardant: IEC 60332.1
- Insulation resistance: 10 M© x km
- Smoke density acc. to EN 50268 / IEC 61034
- Corrosiveness of combustion gases acc. to EN 50267-2-2, IEC 60754-2
- Flame test: flame-retardant acc. to EN 50265-2-1, IEC 60332.1