KYORITSU 6010A[Mar. 19, 2009 20:51:07]
Specification
Continuity and Insulation Testing :
• Live circuit warning LED:
Immediate illumination of a warning lamp if the circuit under test is live
• Auto Discharge:
Allows fast and safe discharge of electrical energy stored in capacitive circuits following testing
• Integral overload protection on internal continuity and insulation test circuitry
• Autoranging
• 500V DC test voltage for insulation tests
• 200mA short circuit current on continuity ranges
Loop and RCD Testing :
• Wiring connection check LED’s:
Immediate indication if wiring of circuit under test is correct
• Overheat Protection:
Rapid detection of overheating of internal circuitry,display of warning signal to user and automatic halting of measurement
• Supply Voltage Indication:
Can display supply voltage value in loop impedance mode
• Low Current Loop Impedance Test:
Short duration low test current will prevent tripping of many passive RCDs
• Auto Data Hold:
Retains displayed reading for set period following test
• Phase Angle Selection:
Selection of test current from +ve or -ve half cycle of waveform can prevent tripping of polarized type RCDs
Continuity Testing :
- Measuring Ranges : 0~19.99 and 10.0~199.9© (2 auto ranges)
- Open Circuit Voltage : > 4V (as per IEC 364)
- Short Circuit Current : > 200mA DC (as per IEC 364)
- Accuracy : ±(3% + 3dgt)
Loop Impedance Testing :
- Rated Voltage : 230V AC +10%-15% (50Hz)
- Voltage Measuring Range : 100-250V AC (50Hz)
- Impedance Range
Nominal Test Current : 20/2000©
25A (20© range) 15mA (2000© range)
- Test Period : 1/2 cycle (10ms)
- Accuracy : 20© range : ±(3% + 8dgt) 2000© range : ±(3% + 8dgt)
Insulation Testing :
- Measuring Ranges : 0~19.99 and 10.0~199.9M© (2 auto ranges)
- Test Voltage : 500V DC
- Output Voltage on
Open Circuit : 570V DC±6%
- Rated Current : > 1mA (as per IEC 364)
- Accuracy : ± (3% + 3dgt)
RCD Testing :
- Rated Voltage : 230V AC +10%-15% (50Hz)
- Trip Current Settings : RCD × 1/2: 5, 15, 50, 150, 250mA
RCD × 1: 10, 30, 100, 300, 500mA
- Trip Current Duration : RCD × 1/2 × 1: 2000ms
Fast Trip 150mA
- Accuracy : Trip current ±3% of test current at 230V.
Trip time ±(3% + 3dgt)
General :
- Safety Standard : IEC 61010-1 CAT.III 300V Pollution Degree 2
IEC 61010-2-031
IEC 61557
- Withstand Voltage : 4000V AC for 1 minute
- Power Source : R6P (AA) (1.5V) × 8
- Dimensions : 175(L) × 115(W) × 86(D)mm
- Weight : 780g approx.
- Accessories : 7025 (Test Leads)
KAMP10* (Test Lead with IEC Connector)
Pouch for Test leads
Shoulder Strap
Shoulder Pad
R6P (AA) × 8
Instruction Manual
- Optional : 7133A
* KAMP10(EU): European SHUKO plug
KAMP10(UK): British plug(13A)
KAMP10(AU): Australian plug
KAMP10(SA): South African plug