Specification
� Dust and drip proof.(designed to IEC 529 IP54)
� In addition to the facility for precision measurement, test leads for simplified two wire measuring system also supplied as standard accessories.
(unit can be hung from the neck for simplified measurement)
� Designed to meet IEC 61010-1 safety standard.
� Capable of measuring earth voltage.
� Automatic warning when resistance of auxiliary earth spikes is in excess of tolerance.
� Small and lightweight. Shock resistant new case material.
� 2mA measuring current permits earth resistance tests without tripping earth leakage current breakers in the circuit under test.
Measurement
Ranges Earth Resistance: 0~20©/0~200©/0~2000©
Earth Voltage [50,60Hz]: 0~200V AC
Accuracy Earth Resistance: ±2%rdg±0.1© (20©range)
|±2%rdg±3dgt (200©/2000©range)
Earth Voltage: ±1%rdg±4dgt
Overload Protection Earth Resistance: 280V AC for 10 seconds
across 2 of the 3 terminals
Earth Voltage: 300V AC for 1 minute
Safety Standard IEC 61010-1 CAT.III 300V Pollution Degree 2, IEC 61557
Applicable Standards IEC 60529 IP54
Withstand Voltage 3700V AC for 1 minute
Power Source R6P (AA) (1.5V) � 6
Dimensions 105(L) � 158(W) � 70(D)mm
Weight 550g approx.
Accessories 7095 (Test Leads) � 1set (red-20m, yellow-10m, green-5m)
8032 (Auxiliary earth spikes) � 1set
7127 (Simplified measurement probe) � 1set
R6P (AA) � 6
Neck strap
Instruction Manual
Carrying Case : 4105A (Soft Case)
: 4105A-H (Hard Case)
Optional 7100 (Precision measurement Cord Set)