Specification
• Large transformer jaws of 68mm diameter makes it possible to clamp on all three or four wires (3 phases) together for leakage current measurement.
• True RMS enables an accurate measurement for distorted waveforms.
• Measurement from mA up to
AC 1000A
• Frequency filter switch to eliminate the effect of the harmonics.
• 2 way analogue output terminal:
AC current detected by transformer jaws is converted to AC and DC voltage. Output cord model 7073 (option) is used for monitoring waveform with an oscilloscope or for connecting to a recorder.
• Peak hold function (Response time is selectable for 10ms or 100ms.)
• Data hold function: Allows for easy reading in dimly light or hard-to-reach locations
• Back light in the LCD (Automatically off)
• International safety standard IEC 61010-1 CAT.III 300V
AC A
(50/60Hz) : 200mA/2/20/200/1000A
|±2.5%rdg±5dgt (200mA/2/20A)
|±3.0%rdg±5dgt (200A, 0~500A)
|±5.5%rdg (501~1000A)
AC A
(WIDE) : 200mA/2/20/200/1000A
|±1.8%rdg±5dgt (50/60Hz) (200mA/2/20A)
|±2.0%rdg±5dgt (50/60Hz) (200A, 0~500A)
|±5.0%rdg (50/60Hz) (501~1000A)
Conductor Size : Ø68mm max.
Frequency Response : 40Hz~1kHz
Analogue Output : AC/DC 200mV against 2000 count reading
(100mV at the 1000A range)
Crest Factor : 3.0 or less
Withstand Voltage : 3700V AC for 1 minute
Applicable Standard : IEC 61010-1 CAT.III 300V Pollution degree 2
IEC 61010-2-032
Power Source : 6F22 (9V) × 1 *Continuous measuring time: Approx. 60 hours
Dimensions : 250(L) × 130(W) × 50(D)mm
Weight : Approx. 600g (including battery)
Accessories : 9094 (Carrying Case)
6F22 × 1
Instruction Manual
Optional : 7073 (2WAY Output Cord)