Welcome to
Nanjing Conpo Power Tech. Co., Ltd

Free Member
Nanjing Conpo Power Tech. Co.,  Ltd
Nanjing Conpo Power Tech. Co., Ltd
China
  • Products Catalog

    UPS C6K/ 10K, C6KS/ 10KS, 3C10KS/ 3C15KS/ 3C20KS

    Quantity Order:
    Origin:
    China
    Payment Method:
    Telegraphic Transfer (T/T)
    Pack. & Delivery:
    Standard export packing

    Specification :

    Feature:
    1. True online double conversion technology
    2. Wide input voltage range
    3. Zero transfer time
    4. Protection against all type of power problems
    5. No add-on CNTL unit required for parallel connection
    6. Low initial investment and flexible for future expansion
    7. Highest reliablility and maximum performance for power sharing and redundancy
    8. Equipped with maintenance bypass siwitch
    9. Sealed lead-acid, maintenance free battery
    10. N+ X parallel redundancy and capacity expansion

    Application:
    Servers, Data-center, Critical network devices, Sensitive electric equipment, Telecom.

    Model C6K C10K C6KS C10KS 3C10KS 3C15KS 3C20KS
    Capacity VA/ W 6KVA/ 4.2KW 10KVA/ 7KW 6KVA/ 4.2KW 10KVA/ 7KW 10KVA/ 7KW 15KVA/ 10.5KW 20KVA/ 14KW
    Input Nominal voltage 220/ 230/ 240VAC 380VAC
    Voltage range 180~ 300VAC 304~ 478VAC
    Frequency range 50Hz: 46~ 54Hz; 60Hz: 56~ 64Hz
    Phase Single phase Three phase ( 4wires+ ground)
    Power factor 0.98 0.95
    Connection Hardwired
    Output Voltage 220/ 230/ 240VAC x( 1+ / -2% )
    Frequency Synchronization range( line mode) ; 50 or 60 x( 1+ / -0.2% ) Hz ( Battery mode)
    Phase Single phase
    Wave form Sine wave
    Power factor 0.7
    Voltage distortion 2% THD( Linear load) ; 6% THD( Non-linear load)
    Overload capability 105% ~ 130% for 10min, e 130% for 1s.
    Current crest ratio 3: 1 max
    Connections Hardwired
    Battery Type Sealed, maintenance free, lead-acid
    Nominal
    DC voltage 240VDC
    Quantity 20pcs
    Back-up time( full load) 7min 5min Depends on the requested back-up time
    Recharge time Depends on the capacity of the external battery bank
    Connection Hardwired
    Transfer time 0ms
    Maintenance bypass switch Yes
    Indicator LED display Load level/ Battery level, Battery, Utility power, Inverter, Bypass, Overload, Fault
    LCD display UPS status 1/ P 0/ P voltage frequency, Battery voltage, Battery capacity, loading, Temperature, History record
    Bypass Alarm beeps very two seconds
    Battery discharge Alarm beeps every four seconds, every second if battery low
    Overload Alarm beeps two for every second
    Fault Alarm beeps continuously
    Acoustic noise At 1meter distance d 55dB
    Communications DB-9 port RS-232 series interface
    Intelligent slot Up to three units in parallel for power redundancy and load sharing
    Environment Operating Tem. 0~ 40º C
    Operating Humidity 20~ 90% non-condensing
    Weight Net( kg) 78 81 32.5 42.5 43 58 58
    Dimensions( pkg) WxDxH( mm) 445* 710* 940