YOKOGAWA MY 10 Insulation Tester
Specification
Single rating, Analog type, 5 models
Rating: 125V/ 200MO, 250V/ 200MO, 500V/ 2000MO, 500V/ 1000MO, 1000V/ 2000MO
Features: Automatic discharge function, AC Voltage measurement, Protective covering
Features:
Analog models with single rating
AC voltage measurement
Automatic discharge
A wide choice of accessories
Designed for shared use with the MY40
Specifications:
Scale length: Approx. 107 mm; afterglow-illuminated scale plate
AC voltage measurement: If any AC voltage is present across the test terminals, the tester lets you know by pointing to an AC voltage value and turning on the LED lamp. You can perform AC voltage measurement with the MEAN switch turned off.
Additional functions: Automatic discharge function:
- If the object under test remains electrified after the MEAS switch is turned off, the tester lets you know by turning on the LED lamp. If you leave the tester connected to the electrified object, the tester automatically begins to discharge electricity and then goes out.
- When the object under test is capacitive and electrified, the tester lets you know by turning on the LED lamp. When left connected to the object, the tester automatically discharges electricity, thus preventing possible electric shock or spike noise at power-on.
Battery check: ( BAT mark on the scale plate)
Battery life: Approx. 10 hours when continuously operated on manganese-oxide batteries with the pointer pointing to the central scale value.
Batteries: Four AA ( R6P) batteries
Dimensions: Approx. 125 ( W) Ã 103 ( H) Ã 53 ( D) ( mm) , excluding protrusions
Weight: Approx. 500 g ( main unit and batteries only, excluding accessories)
Compliance: EN61010-1: 1993; EN61010-2-31: 1995 ( Over voltage Category III, Pollution Degree 2 installation