Specification :
The module has been designed to
combine a maximum of 16
generators and 16 mains ( utility)
supplies up to a maximum of 20 in
one system, e.g. 16 generators
and 4 mains ( utility) supplies –
DSE7560 required to synchronise
with the mains ( utility) .
Themodule has the ability to
monitor generator under/ over volts,
over current, generator under/ over
frequency, under speed, over speed,
charge fail, emergency stop, lowoil
pressure, high engine temperature,
fail to start, low/ highDCbattery
volts, fail to stop, generator short
circuit protection, reverse power,
generator phase rotation error, earth
fault protection, loss of speed signal,
fail to open, fail to close, out of sync,
open circuit failure, negative phase
sequence and loss of excitation.